Function Description
10
4/1553-HSC 901 101/2 Uen B 2009-02-27
Good Poor Failed Poor Good Poor Good
State:
Fan rotation speed
Poor Performance Alarm
Good Performance Alarm
Failed Alarm
Threshold 4
Threshold 3
Threshold 2
Threshold 1
Figure 5 Overview of Performance State for the Fans
Table 2 on page 10 lists the thresholds for the different nodes:
Table 2 Temperature Thresholds
Threshold EDN312 (rpm) ESN108 (rpm) EXN104 (rpm)
Threshold 4 11,000 12,000 12,000
Threshold 3 10,000 11,000 11,000
Threshold 2 7,000 10,000 10,000
Threshold 1 6,000 9,000 9,000
A fan changes the state from Good to Poor, if the rotation speed of the fan
in rpm, after 2 minutes of running at full speed level, is below the Threshold
3.